Containment Planning & Design
Like any infrastructure project, structured cabling doesn’t sit in isolation, and the invisible networking that organisations soon come to rely on requires dedicated design and planning to ensure effective rollout, especially when it’s being installed as part of a larger construction project.
As structured cabling specialists, we often work with Mechanical & Electrical (M&E) Contractors and the broader contracting hierarchy, consulting upfront on the best ways to pre-plan containment design to de-risk installation projects.
Our expertise and experience often allow us to help reduce project costs while identifying unforeseen issues, such as lengthy delays and potential damage to other build projects on a site.
Sometimes, the importance of containment sizing, scheduling, and routing to the success of a cabling installation project is underestimated. And that’s why we like to be involved from the off – to bring our expertise to the table.
Here are five key considerations we employ for effective containment design.
Cable Capacity and Future-Proofing
Containment design needs to be robust, efficient, and scalable while making sure the keenest industry standards are met. It must accommodate current and anticipated future cabling capacity needs.
This means considering potential growth in data, power, and communication needs over time to ensure that the system can be expanded without significant disruption or cost.
Understanding an organisation’s growth plans and how these may impact cabling is key. Despite the attraction of minimising up-front costs to create capacity for what you have now, we aim for a 40% fill rate at the initial installation.
This allows cable architecture to be designed more effectively for weight and heat distribution. Sometimes, when too much routing is added into containment channels, cables in the middle or bottom of the stack can become compromised.
We aim for a 40% fill rate
Routing & Design
Maximum cable run lengths and allowances for bend radius can impact containment design. If planned upfront, based on demand, this can minimise expensive retro-fitting projects further down the line.
This not only relates to the 90-metre maximum for the permanent link (patch panel to outlet), but also gives consideration to minimising cable lengths from outlet to device.
This sounds simple, but it is essential to plan upfront. Otherwise, costly additional cabinets and fibre optic backbone may need to be installed to ensure network performance.
The allowance for a suitable bend radius in containment is also critical to ensure optimal cable performance and longevity to prevent strain on the cables, which can lead to signal degradation, attenuation, or even physical damage to the conductors, especially in fibre optic and high-speed data cables.
Spacing, Accessibility and Maintenance
When designing grid outlet positions, sufficient box depth for cables is essential to ensure performance and to minimise degradation. The minimum box depth required to accommodate bend radius for a Cat6 cable is 24mm. With Cat6a, this is now 40mm.
Deeper trunking and access are essential for back boxes, floor boxes and grid outlet positions (GOP), especially with other cabling usually integrated into the same space.
Data cabling installations typically involve more individual cables than other infrastructure and often have more ‘day two’ works, or ‘moves, adds, and changes, than, for example, electrical infrastructure.
Data containment systems must be designed with accessibility in mind, allowing easy access for repairs, upgrades, or replacements without causing disruption to ensure ongoing maintenance is simple, safe, and efficient.
Installation Process
On large contracting projects, primary and secondary containment should be installed end-to-end before any cable installation work commences. This avoids coiling of cables while the project is waiting to be ready for final installation, which can result in costly additional visits, “variation to a project” costs, and potential damage to the cabling itself.
There are also serious implications in terms of health and safety on site if cabling is left waiting for final installation.
Fire Safety and Regulations
Structured cabling systems must comply with fire safety regulations, including the use of fire-rated containment systems where necessary. Cable containment should also help prevent the spread of fire through cable channels. Ensuring that cable routing allows for sufficient ventilation prevents cables from overheating, reducing the fire risk, and regular inspections and adherence to standards will help the system maintain compliance.
Summary
Effective containment design for structured cabling systems is crucial to ensure a reliable and scalable infrastructure in corporate environments. Considering factors such as cable capacity, separation of power and data cables, ease of maintenance, fire safety compliance, and aesthetic integration ensures a well-functioning structured cabling network that supports current needs and future growth.
As a specialist, we understand the potential risks and issues you may face on an M&E project and are here for consultation in advance to help de-risk your project. If you would like to talk to us about a project or you have a question, please get in touch.